Related Resources: fluid flow
Duct Roughness Factors Table
Fluids Engineering Table of Contents
Hydraulic and Pneumatic Engineering
Roughness factors listed in Table 1, are recommended for use with Colebrook Formula.
Duct Roughness Factors Table
Duct Type/Material | Absolute Roughness ε, ft |
|
Range |
Roughness Category |
|
Drawn tubing (Madison and Elliot 1946) | 0.0000015 |
Smooth 0.0000015 |
PVC plastic pipe (Swim 1982) | 0.00003 to 0.00015 |
Medium smooth 0.00015 |
Commercial steel or wrought iron (Moody 1944) | 0.00015 |
|
Aluminum, round, longitudinal seams, crimped slip joints, 3 ft spacing (Hutchinson 1953) | 0.00012 to 0.0002 |
|
Galvanized steel, round, longitudinal seams, variable joints (Vanstone, drawband, welded. Primarily beaded coupling), 4 ft joint spacing (Griggs et al. 1987) |
0.00016 to 0.00032 |
Average 0.0003 |
Galvanized steel, spiral seams, 10 ft joint spacing (Jones 1979) | 0.0002 to 0.0004 |
|
Galvanized steel, spiral seam with 1, 2, and 3 ribs, beaded couplings, 12 ft joint spacing (Griggs et al. 1987) |
0.00029 to 0.00038 |
|
Galvanized steel, spiral seams, 10 ft joint spacing (Jones 1979) | 0.0002 to 0.0004 |
|
Galvanized steel, spiral seam with 1, 2, and 3 ribs, beaded couplings, 12 ft joint spacing (Griggs et al. 1987) |
0.00029 to 0.00038 |
|
Galvanized steel, rectangular, various type joints (Vanstone, drawband, welded. Beaded coupling), 4 ft spacinga (Griggs and Khodabakhsh-Sharifabad 1992) |
0.00027 to 0.0005 |
|
Phenolic duct, aluminum foil on the interior face, sections connected with a four-bolt flange and cleat joint (Idem and Paruchuri 2018) |
||
5 ft spacing: | 0.00049 to 0.00128 |
|
10 ft spacing | 0.00025 to 0.00098 |
|
Wright Friction Chart: Galvanized steel, round, longitudinal seams, 2.5 ft joint spacing, |
0.0005 |
- |
Flexible duct, nonmetallic and wire, fully extended (Abushakra et al. 2004; Culp 2011) | 0.0003 to 0.003 |
Medium rough 0.003 |
Galvanized steel, spiral, corrugated,b Beaded slip couplings, 10 ft spacing (Kulkarni et al. 2009) | 0.0018 to 0.0030 |
|
Fibrous glass duct liner, air side with facing material (Swim 1978) | 0.005 |
|
Fibrous glass duct liner, air side spray coated (Swim 1978) | 0.015 |
Rough 0.01 |
Flexible duct, metallic corrugated, fully extended | 0.004 to 0.007 |
|
Concrete (Moody 1944) | 0.001 to 0.01 |
a Griggs and Khodabakhsh-Sharifabad (1992) showed that ε values for rectangular duct construction combine effects of surface condition, joint spacing, joint type, and duct construction
(cross breaks, etc.), and that the ε-value range listed is representative.
b Spiral seam spacing was 4.65 in. with two corrugations between seams. Corrugations were 0.75 in. wide by 0.23 in. high (semicircle).
Reference:
ASHRAE Handbook of Fundamentals - 2021